top of page
50441

50441

SKU: TR
$43.34Price

50441  - scheinder

closed toroid A type, for Vigirex and Vigilhom, SA200, inner diameter 200 mm, rated current 400 A

stock :7

Description

This toroid is dedicated to Vigilohm Insulation Fault locators, and to VigiPacT type A residual current protection and monitoring relays. It allows the monitoring of the injected component from Vigilohm Insulation Monitor, and the measurement of a current rating up to 400A for VigiPacT monitoring and protection relays. The transformer ratio is 1/1000. The inner diameter of the toroid is 200 millimeters and the weight is 1.320kg. The cables must be centered within the toroid and the diameter represented by all these cables should not exceed 100 millimeters. The maximum cross section per phase (R, S, T, N) is 2 cables of 185mm² for a copper conductor.

Quantity
Only 7 left in stock
  • Specifications Main

    Main
    Range VigiPacT
    Device short name SA200
    Product or component type Earth leakage current sensor
    Device application Equipment monitoring and control
    Range compatibility VigiPacT RH10M residual current protection relay
    VigiPacT RH10P residual current protection relay
    VigiPacT RH21M residual current protection relay
    VigiPacT RH21P residual current protection relay
    VigiPacT RH68M residual current protection relay
    VigiPacT RH86M residual current protection relay
    VigiPacT RH86P residual current protection relay
    VigiPacT RH99M residual current protection relay
    VigiPacT RH99P residual current protection relay
    VigiPacT RH197M residual current protection relay
    VigiPacT RH197P residual current protection relay
    VigiPacT RHU residual current protection relay
    VigiPacT RHUs residual current protection relay
    VigiPacT RMH residual current protection relay
    current sensor type A type closed toroid
    [Ie] rated operational current 400 A
  • Complementary and Environment

    Complementary
    Transformer ratio 1/1000
    network type AC/DC
    network frequency 45...440 Hz
    [Icw] rated short-time withstand current 85 kA for 0.5 s
    Residual short-circuit withstand current 85 kA / 0.5 s conforming to IEC 60947-2
    [Ui] rated insulation voltage 1000 V
    Overvoltage category IV
    [Uimp] rated impulse withstand voltage 12 kV
    Mounting mode Fixed (cables)
    Fixed (plain backplate)
    Fixed (profiled sheet metal)
    Fixed (slotted backplate)
    Calorific value 7.05 MJ
    Connections - terminals Screw connection 0.22 mm²
    Diameter 196 mm inner:
    Cable outer diameter 100 mm for 2 cables : 185 mm² (maximum)
    Net weight 1.32 kg
    Height 256 mm
    Width 274 mm
    Depth 46 mm
    Environment
    IP degree of protection Connectors: IP20
    IP30
    Environmental characteristic Exposure to damp heat not in service (25...55 °C, RH 95 %) : 28 cycles conforming to IEC 60068-2-30
    Salt mist: Kb/2 conforming to IEC 60068-2-52
    Exposure to damp heat in service: category C2: 48 hours conforming to IEC 60068-2-56
    Pollution degree Level 3 conforming to IEC 60664-1
    Ambient air temperature for operation -35…70 °C
    Ambient air temperature for storage -55…85 °C
    Standards IEC 60947-2
    Product certifications CE
    Packing Units
    Unit Type of Package 1 PCE
    Number of Units in Package 1 1
    Package 1 Height 7.500 cm
    Package 1 Width 27.000 cm
    Package 1 Length 28.400 cm
    Package 1 Weight 1.100 kg
    Unit Type of Package 2 S04
    Number of Units in Package 2 12
    Package 2 Height 30.000 cm
    Package 2 Width 40.000 cm
    Package 2 Length 60.000 cm
    Package 2 Weight 13.800 kg
    Unit Type of Package 3 P12
    Number of Units in Package 3 48
    Package 3 Height 50.000 cm
    Package 3 Width 80.000 cm
    Package 3 Length 120.000 cm
    Package 3 Weight 67.864 kg
No Reviews YetShare your thoughts. Be the first to leave a review.
bottom of page