A9F74120
A9F74120 - scheinder
Miniature circuit breaker, Acti9 iC60N, 1P, 20 A, C curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)
stock : 36Description
This Acti9 iC60N is a low voltage miniature circuit breaker (MCB). It is a 1P circuit breaker with 1 protected pole, 20A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 220VAC to 240VAC conforming to EN/IEC 60947-2 standard and 6000A at 230VAC conforming to EN/IEC 60898-1 standard. It complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. This miniature circuit breaker protects circuits against short circuit and overload current. Its unique VisiTrip indicator reduces intervention time by showing the faulty circuit. Its VisiSafe green strip guarantees the physical opening of the contacts to allow downstream maintenance. Its fast closing mechanism independent of manual operation improves its service life. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ui rated insulation voltage is 500VAC. Its limitation class 3 (according to EN/IEC60898-1) improves downstream circuit protection cost. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is white (RAL9003). The dimensions are (W) 18mm x (H) 85mm x (D) 78.5mm. The weight is 0.215kg. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is -35°C to 70°C. The storage temperature is -40°C to 85°C.
Specifications Main
Main
device application Distribution sherry Act 9 product name Acti9 iC60 Product or component type Miniature circuit breaker Product group IC60N Definition of pole 1P number of protected poles 1 [In] nominal current 20 A Network type AC
DCopening unit technology Thermal Magnetic slope code C cutting capacity 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2
15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2
10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2Usage category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for insulation Yes conforming to TR 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2Standards TR 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2Complement
Network frequency 50/60Hz magnetic opening limit 8 x In +/- 20% [Ics] nominal service interrupting capacity 27 kA 75 % conforming to EN 60947-2 - 12...60 V AC 50/60 Hz
7.5 kA 75 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
27 kA 75 % conforming to IEC 60947-2 - 12...60 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947 -2 - 100...133 V AC 50/60 Hz
15 kA 75 % conforming to EN 60947-2 - 100...133 V AC 50/60 Hz
6000 A 100 % conforming to TR 60898-1 - 230 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 - 230 V AC 50/60 Hz
10 kA 100 % conforming to EN 60947-2 - 72 V DC
10 kA 100 % conforming to IEC 60947-2 - 72 V DC
15 kA 100 % conforming to EN 60947-2 - 12...60 V DC
15 kA 100 % conforming to IEC 60947-2 - 12...60 V DCrestriction class 3 conforming to TR 60898-1
3 conforming to IEC 60898-1[Ui] nominal insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage Conforming to 6 kV EN 60947-2
Conforming to 6 kV IEC 60947-2ignition position indicator Yes Control type Transition On-device signaling Open indicator Mounting Type Still mounting support DIN rail comb busbar distribution block compatibility Top or bottom: YES 9mm screw pitch 2 height 85mm width 18mm Depth 78.5mm Product weight 0.215 kg colour White Mechanical durability 20000 cycles electrical resistance 10000 cycles connections - terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connection tightening torque 2 Nm above or below earth leakage protection None Environment and Packing Units
Environment
IP protection degree
IP20 conforming to IEC 60529degree of contamination 3 conforming to EN 60947-2
3 conforming to IEC 60947-2overvoltage category IV tropical climate 2 conforming to IEC 60068-1 relative humidity 95% at 55 °C working height 0...2000m Nominal operating ambient temperature -35…70 °C Storage environmental conditions -40…85 °C Packaging units
Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 1,800 cm Package 1 Width 7,300 cm Package 1 Length 9,500 cm Package 1 Weight 114,000g Unit Type of Package 2 BB1 Number of Units in Package 2 12 Package 2 Height 8,000 cm Package 2 Width 10,000 cm Package 2 Length 22,500 cm Package 2 Weight 1,424 kg Unit Type of Package 3 S03 Number of Units in Package 3 132 Package 3 Height 30,000 cm Package 3 Width 30,000 cm Package 3 Length 40,000 cm Package 3 Weight 16,160 kg properties
Miniature circuit breaker, Acti9 iC60N, 1P, 20 A, C curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)
A9F74120
Definition of pole:1P
Nominal current (Ir): 20 A
slope code: C
- Compliance with industrial insulation according to IEC/EN 60947-2 standard
- Combines short circuit and overload current protection
- Visitrip system for rapid detection of faulty outputs for shorter repair times
- VisiSafe system offering advanced security when it comes to circuit protection
- Option to add auxiliary devices, remote monitoring and residual current device (Vigi)
- Environmental performance of the product More information