ATV31H037M2
ATV31H037M2 - SCHNEIDER
variable speed drive ATV31 - 0.37kW - 240V 1-phase supply - EMC filter - IP20
In Stock
Specifications
Range of product: Altivar
product or component type: Variable speed drive
Product specific application: Simple machine
Component name: ATV31
Assembly style: With heat sink
EMC filter: Integrated
[Us] rated supply voltage: 200...240 V - 5...5 %
Supply frequency: 50...60 Hz - 5...5 %
Network number of phases: Single phase
Motor power Kw: 0.37 kW 4 kHz
Motor power hp: 0.5 hp 4 kHz
Line current: 4.4 A at 240 V
5.3 A at 200 V, Isc = 1 kA
Apparent power: 1 kVA
Prospective line Isc: 1 kA
Nominal output current: 3.3 A 4 kHz
Maximum transient current: 5 A for 60 s
Power dissipation in W: 41 W at nominal load
Asynchronous motor control profile: Sensorless flux vector control with PWM type motor control signal
Factory set : constant torque
analogue input number: 3
Complementary
product destination Asynchronous motors Supply voltage limits 170…264 V Network frequency 47.5...63 Hz Output frequency 0.0005…0.5 kHz Nominal switching frequency 4 kHz Switching frequency 2...16 kHz adjustable Speed range 1…50 Transient overtorque 150…170 % of nominal motor torque Braking torque <= 150 % during 60 s with braking resistor
100 % with braking resistor continuously
150 % without braking resistorRegulation loop Frequency PI regulator Motor slip compensation Suppressable
Automatic whatever the load
AdjustableOutput voltage <= power supply voltage Electrical connection Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1...LI6 terminal 2.5 mm² AWG 14
L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- terminal 2.5 mm² AWG 14Tightening torque Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1...LI6: 0.6 N.m
L1, L2, L3, U, V, W, PA, PB, PA/+, PC/-: 0.8 N.minsulation Electrical between power and control Supply Internal supply for logic inputs: 19...30 V 100 mA, protection type: overload and short-circuit protection
Internal supply for reference potentiometer (2.2 to 10 kOhm): 10...10.8 V 10 mA, protection type: overload and short-circuit protectionAnalogue input type AI3 configurable current 0...20 mA, impedance: 250 Ohm
AI1 configurable voltage 0...10 V, input voltage 30 V max, impedance: 30000 Ohm
AI2 configurable voltage +/- 10 V, input voltage 30 V max, impedance: 30000 OhmSampling duration LI1...LI6: 4 ms discrete
AI1, AI2, AI3: 8 ms analogResponse time AOV, AOC 8 ms for analog
R1A, R1B, R1C, R2A, R2B 8 ms for discreteLinearity error +/- 0.2 % for output analogue output number 2 Analogue output type AOC configurable current: 0...20 mA, impedance: 800 Ohm, resolution: 8 bits
AOV configurable voltage: 0...10 V, impedance: 470 Ohm, resolution: 8 bitsDiscrete input logic Positive logic (source) (LI1...LI6), < 5 V (state 0), > 11 V (state 1)
Logic input not wired (LI1...LI4), < 13 V (state 1)
Negative logic (source) (LI1...LI6), > 19 V (state 0)Discrete output number 2 Discrete output type Configurable relay logic: (R1A, R1B, R1C) 1 NO + 1 NC - 100000 cycles
Configurable relay logic: (R2A, R2B) NC - 100000 cyclesMinimum switching current R1-R2 10 mA at 5 V DC Maximum switching current R1-R2: 2 A at 250 V AC inductive load, cos phi = 0.4 and L/R = 7 ms
R1-R2: 2 A at 30 V DC inductive load, cos phi = 0.4 and L/R = 7 ms
R1-R2: 5 A at 250 V AC resistive load, cos phi = 1 and L/R = 0 ms
R1-R2: 5 A at 30 V DC resistive load, cos phi = 1 and L/R = 0 msDiscrete input number 6 Discrete input type (LI1...LI6) programmable at 24 V, 0…100 mA for PLC, impedance: 3500 Ohm Acceleration and deceleration ramps S, U or customized
Linear adjustable separately from 0.1 to 999.9 sBraking to standstill By DC injection Protection type Input phase breaks: drive
Line supply overvoltage and undervoltage safety circuits: drive
Line supply phase loss safety function, for three phases supply: drive
Motor phase breaks: drive
Overcurrent between output phases and earth (on power up only): drive
Overheating protection: drive
Short-circuit between motor phases: drive
Thermal protection: motorInsulation resistance >= 500 mOhm 500 V DC for 1 minute Display type 1 LED (red) for drive voltage
Four 7-segment display units for CANopen bus statusTime constant 5 ms for reference change Frequency resolution Display unit: 0.1 Hz
Analog input: 0.1...100 HzConnector type 1 RJ45 for CANopen via VW3 CANTAP2 adaptor
1 RJ45 for ModbusPhysical interface RS485 multidrop serial link for CANopen via VW3 CANTAP2 adaptor
RS485 multidrop serial link for ModbusTransmission frame RTU for CANopen via VW3 CANTAP2 adaptor
RTU for ModbusTransmission rate 10, 20, 50, 125, 250, 500 kbps or 1 Mbps for CANopen via VW3 CANTAP2 adaptor
4800, 9600 or 19200 bps for ModbusNumber of addresses 1…127 for CANopen via VW3 CANTAP2 adaptor
1…247 for ModbusNumber of drive 127 for CANopen via VW3 CANTAP2 adaptor
31 for Modbusmarking CE Operating position Vertical +/- 10 degree net weight 1.5 kg Environmental
Dielectric strength 2040 V DC between earth and power terminals
2880 V AC between control and power terminalsElectromagnetic compatibility 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3Standards EN 50178 Product certifications CSA
UL
N998
C-TickIP degree of protection On upper part: IP20 (without cover plate)
On connection terminals: IP21
On upper part: IP31
On upper part: IP41Pollution degree 2 protective treatment TC Vibration resistance 1 gn (f= 13…150 Hz) conforming to EN/IEC 60068-2-6
1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6Shock resistance 15 gn for 11 ms conforming to EN/IEC 60068-2-27 Relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
5…95 % without dripping water conforming to IEC 60068-2-3ambient air temperature for storage -25…70 °C Ambient air temperature for operation -10…50 °C without derating (with protective cover on top of the drive)
-10…60 °C with derating factor (without protective cover on top of the drive)Operating altitude <= 1000 m without derating
>= 1000 m with current derating 1 % per 100 m