LC1D18B7
SKU: TR
$18.78Price
LC1D18B7 - scheinder
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 18 A - 24 V AC coil
stock : 41
Explanation
TeSys D contactor, 3 poles (3NO), motor control applications maximum 18A/690V AC-3/3e (7 5kW@400V) Operating rating up to 3600 rpm and high reliability and durability in environments up to 60°C Compact (45 mm wide), DIN rail mounting or screw fixing Multi standard certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh). Multi standard certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh)
Specifications Main
Main Range of product TeSys Deca Product or component type Contactor Device short name LC1D Contactor application Resistive load
Motor controlUtilisation category AC-1
AC-4
AC-3
AC-3ePoles description 3P [Ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz
Power circuit: <= 300 V DC[Ie] rated operational current 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
18 A (at <60 °C) at <= 440 V AC AC-3e for power circuit[Uc] control circuit voltage 24 V AC 50/60 Hz Complementary
Motor power kW 4 kW at 220...230 V AC 50/60 Hz (AC-3)
7.5 kW at 380...400 V AC 50/60 Hz (AC-3)
9 kW at 415...440 V AC 50/60 Hz (AC-3)
10 kW at 500 V AC 50/60 Hz (AC-3)
10 kW at 660...690 V AC 50/60 Hz (AC-3)
4 kW at 400 V AC 50/60 Hz (AC-4)
4 kW at 220...230 V AC 50/60 Hz (AC-3e)
7.5 kW at 380...400 V AC 50/60 Hz (AC-3e)
9 kW at 415...440 V AC 50/60 Hz (AC-3e)
10 kW at 500 V AC 50/60 Hz (AC-3e)
10 kW at 660...690 V AC 50/60 Hz (AC-3e)Motor power hp 1 hp at 115 V AC 50/60 Hz for 1 phase motors
3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
10 hp at 460/480 V AC 50/60 Hz for 3 phases motors
15 hp at 575/600 V AC 50/60 Hz for 3 phases motorsCompatibility code LC1D Pole contact composition 3 NO Protective cover With [Ith] conventional free air thermal current 10 A (at 60 °C) for signalling circuit
32 A (at 60 °C) for power circuitIrms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
300 A at 440 V for power circuit conforming to IEC 60947Rated breaking capacity 300 A at 440 V for power circuit conforming to IEC 60947 [Icw] rated short-time withstand current 145 A 40 °C - 10 s for power circuit
240 A 40 °C - 1 s for power circuit
40 A 40 °C - 10 min for power circuit
84 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuitAssociated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
50 A gG at <= 690 V coordination type 1 for power circuit
35 A gG at <= 690 V coordination type 2 for power circuitAverage impedance 2.5 mOhm - Ith 32 A 50 Hz for power circuit Power dissipation per pole 2.5 W AC-1
0.8 W AC-3
0.8 W AC-3e[Ui] rated insulation voltage Power circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certifiedOvervoltage category III Pollution degree 3 [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947 Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1Mechanical durability 15 Mcycles Electrical durability 1.65 Mcycles 18 A AC-3 at Ue <= 440 V
1 Mcycles 32 A AC-1 at Ue <= 440 V
1.65 Mcycles 18 A AC-3e at Ue <= 440 VControl circuit type AC at 50/60 Hz standard Coil technology Without built-in suppressor module Control circuit voltage limits 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 HzInrush power in VA 70 VA 60 Hz cos phi 0.75 (at 20 °C)
70 VA 50 Hz cos phi 0.75 (at 20 °C)Hold-in power consumption in VA 7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
7 VA 50 Hz cos phi 0.3 (at 20 °C)Heat dissipation 2…3 W at 50/60 Hz Operating time 12...22 ms closing
4...19 ms openingMaximum operating rate 3600 cyc/h 60 °C Maximum operating rate 3600 cyc/h at 60 °C Connections - terminals Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 1 1.5…6 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 1…6 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 1.5…6 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: solid without cable endTightening torque Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2Auxiliary contact composition 1 NO + 1 NC Auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1Signalling circuit frequency 25...400 Hz Minimum switching voltage 17 V for signalling circuit Minimum switching current 5 mA for signalling circuit Insulation resistance > 10 MOhm for signalling circuit Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contactMounting support Rail
PlateEnvironment and Packing Units
Environment Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 60947-4-1
IEC 60335-1:Clause 30.2
IEC 60335-2-40:Annex JJ
UL 60335-2-40:Annex JJ
CSA C22.2 No 60947-4-1Product certifications UL
CCC
CSA
Marine
UKCA
EAC
CB SchemeIP degree of protection IP20 front face conforming to IEC 60529 Protective treatment TH conforming to IEC 60068-2-30 Climatic withstand conforming to IACS E10 exposure to damp heat
conforming to IEC 60947-1 Annex Q category D exposure to damp heatPermissible ambient air temperature around the device -40…60 °C
60…70 °C with deratingOperating altitude 0...3000 m Fire resistance 850 °C conforming to IEC 60695-2-1 Flame retardance V1 conforming to UL 94 Mechanical robustness Vibrations contactor open (2 Gn, 5...300 Hz)
Vibrations contactor closed (4 Gn, 5...300 Hz)
Shocks contactor open (10 Gn for 11 ms)
Shocks contactor closed (15 Gn for 11 ms)Height 77 mm Width 45 mm Depth 86 mm Net weight 0.33 kg Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 5.200 cm Package 1 Width 11.300 cm Package 1 Length 9.500 cm Package 1 Weight 355.000 g Unit Type of Package 2 S02 Number of Units in Package 2 20 Package 2 Height 15.000 cm Package 2 Width 30.000 cm Package 2 Length 40.000 cm Package 2 Weight 7.537 kg Unit Type of Package 3 P06 Number of Units in Package 3 320 Package 3 Height 75.000 cm Package 3 Width 60.000 cm Package 3 Length 80.000 cm Package 3 Weight 129.515 kg properties
New modern look & feel of all machines"
notification_ok
- "Designed to meet the requirements of industrial and HVAC applications"
- "Easier to install and operate with multi-standard screws"
- "With IEC60335-1 compliance, improved fire resistance, and dustproof auxiliaries"
- "Digital customer experience for technical documents
No Reviews YetShare your thoughts.
Be the first to leave a review.

