TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 50A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 15HP at 200 to 208VAC, 15HP at 240VAC, 40HP at 480VAC and 40HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 7.5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 110A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
Specifications Main
Range TeSys
TeSys DecaRange of Product TeSys Deca Product or Component Type Contactor Device short name LC1D contactor application Resistive load
Motor controlutilisation category AC-4
AC-1
AC-3
AC-3ePoles description 3P [Ue] rated operational voltage Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC[Ie] rated operational current 50 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
50 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit[Uc] control circuit voltage 24 V DC Complementary
Motor power kW 15 kW at 220...230 V AC 50/60 Hz (AC-3)
22 kW at 380...400 V AC 50/60 Hz (AC-3)
30 kW at 500 V AC 50/60 Hz (AC-3)
33 kW at 660...690 V AC 50/60 Hz (AC-3)
25 kW at 415 V AC 50/60 Hz (AC-3)
30 kW at 440 V AC 50/60 Hz (AC-3)
11 kW at 400 V AC 50/60 Hz (AC-4)
15 kW at 220...230 V AC 50/60 Hz (AC-3e)
22 kW at 380...400 V AC 50/60 Hz (AC-3e)
30 kW at 500 V AC 50/60 Hz (AC-3e)
33 kW at 660...690 V AC 50/60 Hz (AC-3e)
25 kW at 415 V AC 50/60 Hz (AC-3e)
30 kW at 440 V AC 50/60 Hz (AC-3e)Maximum Horse Power Rating 3 hp at 115 V AC 50/60 Hz for 1 phase motors
7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
15 hp at 200/208 V AC 50/60 Hz for 3 phase motors
15 hp at 230/240 V AC 50/60 Hz for 3 phase motors
40 hp at 460/480 V AC 50/60 Hz for 3 phase motors
40 hp at 575/600 V AC 50/60 Hz for 3 phase motorsCompatibility code LC1D Pole contact composition 3 NO Protective cover With [Ith] conventional free air thermal current 10 A (at 140 °F (60 °C)) for signalling circuit
80 A (at 140 °F (60 °C)) for power circuitIrms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
900 A at 440 V for power circuit conforming to IEC 60947Rated breaking capacity 900 A at 440 V for power circuit conforming to IEC 60947 [Icw] rated short-time withstand current 400 A 104 °F (40 °C) - 10 s for power circuit
810 A 104 °F (40 °C) - 1 s for power circuit
84 A 104 °F (40 °C) - 10 min for power circuit
208 A 104 °F (40 °C) - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuitAssociated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
100 A gG at <= 690 V coordination type 1 for power circuit
100 A gG at <= 690 V coordination type 2 for power circuitAverage impedance 1.5 mOhm - Ith 80 A 50 Hz for power circuit Power dissipation per pole 3.7 W AC-3
9.6 W AC-1
3.7 W AC-3e[Ui] rated insulation voltage Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Power circuit 690 V IEC 60947-4-1Overvoltage category III Pollution degree 3 [Uimp] rated impulse withstand voltage 6 kV IEC 60947 Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1Mechanical durability 10 Mcycles Properties
Electrical durability 1.45 Mcycles 50 A AC-3 <= 440 V
0.5 Mcycles 80 A AC-1 <= 440 V
1.45 Mcycles 50 A AC-3e <= 440 VControl circuit type DC standard Coil technology Built-in bidirectional peak limiting diode suppressor Control circuit voltage limits 0.1...0.3 Uc -40…158 °F (-40…70 °C) drop-out DC
0.75...1.25 Uc -40…140 °F (-40…60 °C) operational DC
1...1.25 Uc 140…158 °F (60…70 °C) operational DCInrush power in W 19 W 68 °F (20 °C)) Hold-in power consumption in W 7.4 W 68 °F (20 °C) Operating time 50 ±15 % ms closing
16...24 ms openingTime constant 34 ms Maximum operating rate 3600 cyc/h 140 °F (60 °C) Connections - terminals Control circuit: screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) - cable stiffness: solid without cable end
Power circuit: screw connection 1 0.00…0.05 in² (1…35 mm²) - cable stiffness: flexible without cable end
Power circuit: screw connection 2 0.00…0.04 in² (1…25 mm²) - cable stiffness: flexible without cable end
Power circuit: screw connection 1 0.00…0.05 in² (1…35 mm²) - cable stiffness: flexible with cable end
Power circuit: screw connection 2 0.00…0.04 in² (1…25 mm²) - cable stiffness: flexible with cable end
Power circuit: screw connection 1 0.00…0.05 in² (1…35 mm²) - cable stiffness: solid without cable end
Power circuit: screw connection 2 0.00…0.04 in² (1…25 mm²) - cable stiffness: solid without cable endTightening torque Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Power circuit 70.81 lbf.in (8 N.m) EverLink BTR screw connectors 0.04…0.05 in² (25…35 mm²) hexagonal 0.16 in (4 mm)
Power circuit 44.25 lbf.in (5 N.m) EverLink BTR screw connectors 0.00…0.04 in² (1…25 mm²) hexagonal 0.16 in (4 mm)
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Power circuit 22.13 lbf.in (2.5 N.m) screw clamp terminals pozidriv No 2Auxiliary contact composition 1 NO + 1 NC Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1Signalling circuit frequency 25...400 Hz Minimum switching voltage 17 V for signalling circuit Minimum switching current 5 mA for signalling circuit Insulation resistance > 10 MOhm for signalling circuit Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contactMounting Support Plate
RailEnvironment & standard
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1Product Certifications UL
GOST
DNV
LROS (Lloyds register of shipping)
CCC
GL
CSA
RINA
BVIP degree of protection IP20 front face IEC 60529 Protective treatment THIEC 60068-2-30 Climatic withstand IACS E10 exposure to damp heat
IEC 60947-1 Annex Q category D exposure to damp heatPermissible ambient air temperature around the device -40…140 °F (-40…60 °C)
140…158 °F (60…70 °C) with deratingOperating altitude 0...9842.52 ft (0...3000 m) Fire resistance 1562 °F (850 °C) IEC 60695-2-1 Flame retardance V1 conforming to UL 94 Mechanical robustness Vibrations contactor open 2 Gn, 5...300 Hz)
Vibrations contactor closed 4 Gn, 5...300 Hz)
Shocks contactor closed 15 Gn for 11 ms)
Shocks contactor open 10 Gn for 11 ms)Height 4.80 in (122 mm) Width 2.17 in (55 mm) Depth 4.72 in (120 mm) Net Weight 2.05 lb(US) (0.93 kg) Ordering and shipping details Category US10I1222358 Discount Schedule 0I12 GTIN 3389119408783 Returnability Yes Country of origin FR Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 2.44 in (6.200 cm) Package 1 Width 5.39 in (13.700 cm) Package 1 Length 5.98 in (15.200 cm) Package 1 Weight 35.24 oz (999.000 g) Unit Type of Package 2 S02 Number of Units in Package 2 10 Package 2 Height 5.91 in (15.000 cm) Package 2 Width 11.81 in (30.000 cm) Package 2 Length 15.75 in (40.000 cm) Package 2 Weight 22.62 lb(US) (10.260 kg)