LC1E1210M5
LC1E1210M5 - SCHNEIDER
Contactor,Easy TeSys Control,LC1E,3P(3NO),AC-3,<=440V,12A,220V AC coil,50Hz,1NO auxiliary contact
In Stock
Description
EasyPact TVS contactor 3 poles for motor applications up to 120A 59kW@440V. It provides a 220V 50Hz AC coil, 3NO built-in auxiliary contacts, power and control connections by screw clamp terminals. 120mm width for standard operating rates up to 1200 cycles per hour. It procures standard reliability and durability with 0.8 Mcycles electrical durability AC-3 and 4 Mcycles mechanical durability. It can cover -5°C to 55°C working temperature and mounted by DIN-rail, No derating up to 3000m altitude. Multi-standards certified (IEC, CCC, EAC) and Green Premium compliant (RoHs/Reach).
GTIN 4011209048645
Specifications
Range Easy TeSys Range of product Easy TeSys Control product or component type Contactor Device short name LC1E contactor application Resistive load
Motor controlUtilisation category AC-3
AC-1Poles description 3P [Ue] rated operational voltage Power circuit: <= 690 V AC 50/60 Hz [Ie] rated operational current 25 A (at <55 °C) at <= 440 V AC AC-1 for power circuit
12 A (at <55 °C) at <= 440 V AC AC-3 for power circuit[Uc] control circuit voltage 220 V AC 50 Hz Complementary
Motor power kW 3 kW at 220...230 V AC 50/60 Hz (AC-3)
5.5 kW at 380...400 V AC 50/60 Hz (AC-3)
5.5 kW at 415 V AC 50/60 Hz (AC-3)
5.5 kW at 440 V AC 50/60 Hz (AC-3)
7.5 kW at 500 V AC 50/60 Hz (AC-3)
7.5 kW at 660...690 V AC 50/60 Hz (AC-3)Pole contact composition 3 NO [Ith] conventional free air thermal current 25 A (at 55 °C) Irms rated making capacity 120 A at 440 V AC for power circuit conforming to IEC 60947-4-1 Rated breaking capacity 96 A at 440 V for power circuit conforming to IEC 60947 [Icw] rated short-time withstand current 105 A 40 °C - 10 s for power circuit
61 A 40 °C - 60 s for power circuit
30 A 40 °C - 600 s for power circuitAssociated fuse rating 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1
25 A gG at <= 690 V coordination type 1 for power circuitAverage impedance 2.5 mOhm - Ith 25 A 50 Hz for power circuit Power dissipation per pole 0.36 W AC-3
1.6 W AC-1[Ui] rated insulation voltage 690 V conforming to IEC 60947-4-1 Overvoltage category III Pollution degree 3 [Uimp] rated impulse withstand voltage 6 kV coil not connected to the power circuit conforming to IEC 60947 Mechanical durability 10000000 cycles Electrical durability 1400000 cycles AC-3
300000 cycles AC-1Control circuit type AC at 50 Hz Control circuit voltage limits 0.85...1.1 Uc (-5…55 °C):operational 50 Hz
0.3...0.6 Uc (-5…55 °C):drop-out 50 HzInrush power in VA 95 VA 50 Hz cos phi 0.75 (at 20 °C)
95 VA 60 Hz cos phi 0.75 (at 20 °C)Hold-in power consumption in VA 8.3 VA 50 Hz cos phi 0.3 (at 20 °C)
8.5 VA 60 Hz cos phi 0.3 (at 20 °C)Heat dissipation 2…3 W for control circuit Operating time 12...22 ms on closing
4...19 ms on openingMaximum operating rate 1800 cyc/h 60 °C Environmental
Standards IEC 60947-5-1
IEC 60947-4-1
IEC 60947-1Product certifications EAC
CEIP degree of protection IP2X conforming to IEC 60529 Protective treatment TH (pollution degree 3) conforming to IEC 60068-2-30 test Db Permissible ambient air temperature around the device -20…70 °C at Uc
-60…80 °C storage
-5…55 °C operationOperating altitude 3000 m without derating Fire resistance 850 °C conforming to IEC 60695-2-1 Mechanical robustness Vibrations contactor open (1.5 Gn, 5...300 Hz)
Vibrations contactor closed (3 Gn, 5...300 Hz)
Shocks contactor open (7 Gn for 11 ms)
Shocks contactor closed (10 Gn for 11 ms)Height 74 mm Width 45 mm Depth 80 mm net weight 0.3 kg