top of page
LC1E1810M5

LC1E1810M5

SKU: TR
$11.39Price

LC1E1810M5 - SCHNEIDER

Contactor,Easy TeSys Control,LC1E,3P(3NO),AC-3,<=440V,18A,220V AC coil,50Hz,1NO auxiliary contact

In Stock

Description

 EasyPact TVS contactor for motor applications up to 18A 9kW@440V 220V 50Hz AC coil, 1NO internal auxiliary contacts provide power and control connections with screw clamps 45 mm width for standard operating speeds up to 1800 cycles per hour 1.2 Mcycle electrical endurance AC- Provides standard reliability and durability with 3 and 10 Mcycle mechanical strength Can cover operating temperature from -5°C to 55°C and is DIN rail mounted, no derating up to 3000m altitude Multi standard certified (IEC, CCC, EAC) and Green Premium compliant ( RoHs/Reach) Multi standard certified (IEC, CCC, EAC) and Green Premium compliant (RoHs/Reach)

Quantity
  • Specifications

    Main
    Range Easy TeSys
    Range of product Easy TeSys Control
    product or component type Contactor
    Device short name LC1E
    contactor application Resistive load
    Motor control
    Utilisation category AC-3
    AC-1
    Poles description 3P
    [Ue] rated operational voltage Power circuit: <= 690 V AC 50/60 Hz
    [Ie] rated operational current 32 A (at <55 °C) at <= 415 V AC AC-1 for power circuit
    18 A (at <55 °C) at <= 440 V AC AC-3 for power circuit
    [Uc] control circuit voltage 220 V AC 50 Hz
  • Complementary

    Motor power kW 4 kW at 220...230 V AC 50/60 Hz (AC-3)
    7.5 kW at 380...400 V AC 50/60 Hz (AC-3)
    9 kW at 415 V AC 50/60 Hz (AC-3)
    9 kW at 440 V AC 50/60 Hz (AC-3)
    10 kW at 500 V AC 50/60 Hz (AC-3)
    10 kW at 660...690 V AC 50/60 Hz (AC-3)
    Pole contact composition 3 NO
    [Ith] conventional free air thermal current 32 A (at 55 °C)
    Irms rated making capacity 180 A at 440 V AC for power circuit conforming to IEC 60947-4-1
    Rated breaking capacity 144 A at 440 V for power circuit conforming to IEC 60947
    [Icw] rated short-time withstand current 145 A 40 °C - 10 s for power circuit
    84 A 40 °C - 60 s for power circuit
    40 A 40 °C - 600 s for power circuit
    Associated fuse rating 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1
    35 A gG at <= 690 V coordination type 1 for power circuit
    Average impedance 2.5 mOhm - Ith 32 A 50 Hz for power circuit
    Power dissipation per pole 0.81 W AC-3
    2.6 W AC-1
    [Ui] rated insulation voltage 690 V conforming to IEC 60947-4-1
    Overvoltage category III
    Pollution degree 3
    [Uimp] rated impulse withstand voltage 6 kV coil not connected to the power circuit conforming to IEC 60947
    Mechanical durability 10000000 cycles
    Electrical durability 300000 cycles AC-1
    1200000 cycles AC-3
    Control circuit type AC at 50 Hz
    Control circuit voltage limits 0.85...1.1 Uc (-5…55 °C):operational 50 Hz
    0.3...0.6 Uc (-5…55 °C):drop-out 50 Hz
    Inrush power in VA 95 VA 50 Hz cos phi 0.75 (at 20 °C)
    95 VA 60 Hz cos phi 0.75 (at 20 °C)
    Hold-in power consumption in VA 8.3 VA 50 Hz cos phi 0.3 (at 20 °C)
    8.5 VA 60 Hz cos phi 0.3 (at 20 °C)
    Heat dissipation 2…3 W for control circuit
  • Environmental

    Standards IEC 60947-5-1
    IEC 60947-4-1
    IEC 60947-1
    Product certifications EAC
    CE
    IP degree of protection IP2X conforming to IEC 60529
    Protective treatment TH (pollution degree 3) conforming to IEC 60068-2-30 test Db
    Permissible ambient air temperature around the device -20…70 °C at Uc
    -60…80 °C storage
    -5…55 °C operation
    Operating altitude 3000 m without derating
    Fire resistance 850 °C conforming to IEC 60695-2-1
    Mechanical robustness Vibrations contactor open (1.5 Gn, 5...300 Hz)
    Vibrations contactor closed (3 Gn, 5...300 Hz)
    Shocks contactor open (7 Gn for 11 ms)
    Shocks contactor closed (10 Gn for 11 ms)
    Height 74 mm
    Width 45 mm
    Depth 80 mm
    net weight 0.3 kg
No Reviews YetShare your thoughts. Be the first to leave a review.