LP1K0901BD
LP1K0901BD - SCHNEIDER
Contactor, TeSys K, 3P, AC-3, lt or eq to 440V, 9A, 1 NC aux, 24VDC coil
In StockDescription
LP1K0901BD is a compact 3-pole TeSys K contactor from Schneider Electric for motor applications. Rated 9A AC-3 4kW@400V, it includes a 24V DC coil and 1NC auxiliary contact allowing easy integration to all control systems. LP1K0901BD is a 3-pole TeSys K contactor from Schneider Electric for simple motor applications rated up to 4kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it can be easily integrated into all control systems thanks to its 24V DC coil and 1NC built-in auxiliary contact. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 45mm wide, for DIN-rail and panel mounting. Ready for connection to all control systems thanks to a 24V DC control voltage and 1NC built-in auxiliary contact. Optimized for simple power applications. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).
Specifications
Range TeSys Product or Component Type Contactor Device short name LP1K contactor application Resistive load
Motor controlComplementary
Utilisation category AC-3
AC-3e
AC-1
AC-4poles description 3P power pole contact composition 3 NO [Ue] rated operational voltage Power circuit <= 690 V AC <= 400 Hz
Signalling circuit <= 690 V AC <= 400 Hz[Ie] rated operational current 9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
20 A (at <140 °F (60 °C)) at <= 690 V AC AC-1 for power circuitControl circuit type DC standard [Uc] control circuit voltage 24 V DC Motor power kW 2.2 kW 220...230 V AC 50/60 Hz AC-3
4 kW 380...415 V AC 50/60 Hz AC-3
4 kW 440/690 V AC 50/60 Hz AC-3
2.2 kW 220...230 V AC 50/60 Hz AC-3e
4 kW 380...415 V AC 50/60 Hz AC-3e
4 kW 440/690 V AC 50/60 Hz AC-3e
2.2 kW 220...230 V AC 50/60 Hz AC-4
4 kW 380...415 V AC 50/60 Hz AC-4
4 kW 440/690 V AC 50/60 Hz AC-4auxiliary contact composition 1 NC [Uimp] rated impulse withstand voltage 8 kV Overvoltage category III [Ith] conventional free air thermal current 20 A (at 140 °F (60 °C)) for power circuit
10 A (at 122 °F (50 °C)) for signalling circuitIrms rated making capacity 110 A AC for power circuit conforming to IEC 60947
110 A AC for signalling circuit conforming to IEC 60947Rated breaking capacity 110 A at 220...230 V conforming to IEC 60947
110 A at 380...400 V conforming to IEC 60947
110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947[Icw] rated short-time withstand current 90 A 122 °F (50 °C) - 1 s for power circuit
85 A 122 °F (50 °C) - 5 s for power circuit
80 A 122 °F (50 °C) - 10 s for power circuit
60 A 122 °F (50 °C) - 30 s for power circuit
45 A 122 °F (50 °C) - 1 min for power circuit
40 A 122 °F (50 °C) - 3 min for power circuit
20 A 122 °F (50 °C) - >= 15 min for power circuit
80 A - 1 s for signalling circuit
90 A - 500 ms for signalling circuit
110 A - 100 ms for signalling circuitAssociated fuse rating 25 A gG at <= 440 V for power circuit
25 A aM for power circuit
10 A gG for signalling circuit conforming to IEC 60947
10 A gG for signalling circuit conforming to VDE 0660Average impedance 3 mOhm - Ith 20 A 50 Hz for power circuit [Ui] rated insulation voltage Power circuit 600 V UL 508
Power circuit 690 V IEC 60947-4-1
Signalling circuit 690 V IEC 60947-4-1
Signalling circuit 690 V IEC 60947-5-1
Signalling circuit 600 V UL 508
Power circuit 600 V CSA C22.2 No 14
Signalling circuit 600 V CSA C22.2 No 14Insulation resistance > 10 MOhm for signalling circuit Inrush power in W 3 W 68 °F (20 °C)) Hold-in power consumption in W 3 W 68 °F (20 °C) Heat dissipation 1.3 W Control circuit voltage limits Operational: 0.8...1.15 Uc (at <122 °F (50 °C))
Drop-out: >= 0.10 Uc (at <122 °F (50 °C))Connections - terminals Screw clamp terminals 1 0.00…0.01 in² (1.5…4 mm²)solid
screw clamp terminals 1 0.00…0.01 in² (0.75…4 mm²)flexible without cable end
screw clamp terminals 1 0.00…0.00 in² (0.34…2.5 mm²)flexible with cable end
screw clamp terminals 2 0.00…0.01 in² (1.5…4 mm²)solid
screw clamp terminals 2 0.00…0.01 in² (0.75…4 mm²)flexible without cable end
screw clamp terminals 2 0.00…0.00 in² (0.34…1.5 mm²)flexible with cable end
Power circuit screw clamp terminals 2 0.00 in² (1.5 mm²)flexible with cable endMaximum operating rate 3600 cyc/h Auxiliary contacts type Instantaneous 1 NC Minimum switching current 5 mA for signalling circuit Minimum switching voltage 17 V for signalling circuit Mounting Support Rail
PlateTightening torque 7.08…11.51 lbf.in (0.8…1.3 N.m) screw clamp terminals Philips No 2
7.08…11.51 lbf.in (0.8…1.3 N.m) screw clamp terminals flat Ø 6 mm
7.08…11.51 lbf.in (0.8…1.3 N.m) screw clamp terminals pozidriv No 2Operating time 30...40 ms coil energisation and NO closing
10 ms coil de-energisation and NO openingSafety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1Mechanical durability 10 Mcycles Electrical durability 1.3 Mcycles 9 A AC-3 <= 440 V
1.3 Mcycles 9 A AC-3e <= 440 V
0.16 Mcycles 20 A AC-1 <= 690 V
0.02 Mcycles 54 A AC-4 <= 440 VHeight 2.28 in (58 mm) Width 1.77 in (45 mm) Depth 2.24 in (57 mm) Net Weight 0.50 lb(US) (0.225 kg) Environmental
Standards EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4Product Certifications CB Scheme
CCC
UL
CSA
EAC
CE
UKCAIP degree of protection IP2X Ambient air temperature for operation -13…122 °F (-25…50 °C) Ambient Air Temperature for Storage -58…176 °F (-50…80 °C) Operating altitude 6561.68 ft (2000 m) without derating Flame retardance V1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102Ordering and shipping details Category US10I1222321 Discount Schedule 0I12 GTIN 3389110363234 Returnability Yes Country of origin ID