top of page
LV431403

LV431403

SKU: TR
$815.00Price

LV431403 - scheinder

circuit breaker basic frame, ComPact NSX250F, 36 kA at 415 VAC 50/60 Hz, 250 A, without trip unit, 3 poles.

stock : 10

description

This base frame comes without trip unit and is compatible with all types of trip units which need to be ordered separately Breaking capacity Icu 36kA / 415VAC 50/60Hz Operating voltage 690VAC 50/60Hz (limited to 440VAC 50/60Hz if earth leakage protection is present) Various optional functions and accessories Can be equipped with Dimensions 105mm x 161mm x 86mm Complies with International Standards (IEC 60947), CCC, EAC and marine specifications Compact NSX250F is part of the Schneider Electric EcoStruxure Power architecture.

Quantity
  • Specifications Main

    Main
    Range ComPact
    Range of product ComPact NSX100...250
    Device short name NSX250F
    Product or component type Basic frame
    Device application Distribution
    Circuit breaker name Compact NSX250F
    Number of poles 3P
    [In] rated current 250 A at 40 °C
    [Ue] rated operational voltage 690 V AC 50/60 Hz
    network type AC
    network frequency 50/60 Hz
    Suitability for isolation Yes conforming to EN/IEC 60947-2
    Utilisation category Category A
    [Icu] rated ultimate short-circuit breaking capacity 85 kA at 240 V AC 50/60 Hz conforming to UL 508
    22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
    35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
    36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    35 kA at 480 V AC 50/60 Hz conforming to UL 508
    30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
    15 kA at 600 V AC 50/60 Hz conforming to UL 508
    Performance level F 36 kA 415 V AC
    Control type Toggle
    mounting mode Fixed
    Complementary
    [Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
    [Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
    [Ics] rated service short-circuit breaking capacity 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
    36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
    30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
    8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    Mechanical durability 20000 cycles conforming to IEC 60947-2
    Electrical durability 10000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
    10000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
    20000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
    5000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
    mounting support Backplate
    Upside connection Front
    downside connection Front
    Connection pitch 35 mm
    Protection type Without protection
    Width (W) 105 mm
    Height (H) 161 mm
    Depth (D) 86 mm
  • Environment

    Environment
    Standards EN/IEC 60947-2
    UL 508
    Product certifications CSA
    UL
    Pollution degree 3 conforming to IEC 60664-1
    IP degree of protection IP40 conforming to IEC 60529
    IK degree of protection IK07 conforming to IEC 62262
    Ambient air temperature for operation -25…70 °C
    Ambient air temperature for storage -50…85 °C
    Packing Units
    Unit Type of Package 1 PCE
    Number of Units in Package 1 1
    Package 1 Height 11.5 cm
    Package 1 Width 14 cm
    Package 1 Length 19.2 cm
    Package 1 Weight 1.592 kg
    Unit Type of Package 2 S04
    Number of Units in Package 2 15
    Package 2 Height 30 cm
    Package 2 Width 40 cm
    Package 2 Length 60 cm
    Package 2 Weight 24.72 kg
No Reviews YetShare your thoughts. Be the first to leave a review.