LV432408
LV432408 - scheinder
circuit breaker basic frame, ComPact NSX400N, 50 kA at 415 VAC 50/60 Hz, 400 A, without trip unit, 4 poles
stock: 10
Description
This base frame comes without trip unit and is compatible with all types of trip units which need to be ordered separately Breaking capacity Icu 50kA / 415VAC 50/60Hz Operating voltage 690VAC 50/60Hz (limited to 440VAC 50/60Hz if earth leakage protection is present) Various optional functions and accessories Can be equipped with Dimensions 185mm x 255mm x 110mm Complies with International Standards (IEC 60947), CCC, EAC and marine specifications Compact NSX400N is part of the Schneider Electric EcoStruxure Power architecture.
Specifications Main
Main Range ComPact Range of product ComPact NSX400...630 Device short name NSX400N Product or component type Basic frame Device application Distribution Circuit breaker name Compact NSX400N Number of poles 4P Neutral position Left [In] rated current 400 A at 65 °C [Ue] rated operational voltage 690 V AC 50/60 Hz network type AC network frequency 50/60 Hz Suitability for isolation Yes conforming to EN/IEC 60947-2 Utilisation category Category A [Icu] rated ultimate short-circuit breaking capacity 85 kA at 240 V AC 50/60 Hz conforming to UL 508
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 480 V AC 50/60 Hz conforming to UL 508
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 600 V AC 50/60 Hz conforming to UL 508
42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2Performance level N 50 kA 415 V AC Control type Toggle mounting mode Fixed Complementary [Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2 [Ics] rated service short-circuit breaking capacity 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2Mechanical durability 15000 cycles conforming to IEC 60947-2 Electrical durability 12000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
3000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
6000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
6000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2mounting support Backplate Upside connection Front downside connection Front Connection pitch 45 mm Protection type Without protection Width (W) 185 mm Height (H) 255 mm Depth (D) 110 mm Environment and Packing Units
Environment Standards EN/IEC 60947-2
UL 508Product certifications UL
CSAPollution degree 3 conforming to IEC 60664-1 IP degree of protection IP40 conforming to IEC 60529 IK degree of protection IK07 conforming to IEC 62262 Ambient air temperature for operation -25…70 °C Ambient air temperature for storage -50…85 °C Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 15.2 cm Package 1 Width 20.3 cm Package 1 Length 29.2 cm Package 1 Weight 5.8 kg Unit Type of Package 2 P12 Number of Units in Package 2 28 Package 2 Height 50.0 cm Package 2 Width 80.0 cm Package 2 Length 120.0 cm Package 2 Weight 175.072 kg