MN undervoltage release, standard, Masterpact MTZ2/3 drawout, 48 VAC 50/60 Hz, 48/60 VDC
| Main | |
| Maximum response time | 95 ms on opening for MasterPact MTZ2 95 ms on opening for MasterPact MTZ3 |
|---|---|
| Range | MasterPact |
| device short name | MN |
| Product or component type | Undervoltage release |
| device application | Safety |
| Range compatibility | Masterpact (MasterPact MTZ2) circuit breaker Masterpact (MasterPact MTZ3) circuit breaker |
| Voltage release type | Instantaneous |
| Complementary | |
| control type | Standard |
|---|---|
| [Un] voltage power supply | 48 V AC 50/60 Hz 48...60 V DC |
| Threshold tripping voltage | 0.35...0.7 Un opening 0.85 Un closing |
| Holding power consumption | 4.5 W |
| Circuit breaker mounting mode | Drawout |
| Packing Units | |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 3.5 cm |
| Package 1 Width | 6.0 cm |
| Package 1 Length | 8.5 cm |
| Package 1 Weight | 176.0 g |
No Reviews YetShare your thoughts.