RH86M
RH86M - schneider
Residual current protection relay, VigiPacT RH86M, 30mA-10A, 220/240VAC 50/60Hz, DIN rail mounting
56500
in stock: 2
description
lay offers reliable protection against electrical faults, ensuring the safety of both personnel and equipment. The RH86M features a fast y-on de-energization time of 0.1 s, providing rapid response to potential risks. Additionally, the relay allows for a maximum adjustable delay-on de-energization time of 10 s and a minimum adjustable delay-on de-energization time of 0.1 s, offering flexibility to suit specific application requirements. This Earth-Leakage Relay is an essential component for electrical systems in residential, commercial, and industrial environments, providing peace of mind and protection against electrical hazards. With its compatibility and advanced features, the RH86M is a reliable and effective solution for earth-leakage protection.
Technicial Specifications Mother
sherry VigiPacT Product group RH86M Product or component type Residual current protection relay relay application Protection relay mounting support DIN rail earth leakage protection class Type A type of setting Selective residual earth leakage sensitivity adjustment type 8 adjustable settings Earth-leakage sensitivity 0.03…10 A Earth-leakage time delay Instantaneous for 0.03 A
Adjustable 6 settings 0…0.5 s for 0.03…10 ACurrent sensors compatibility VigiPacT TOA earth leakage current sensor
VigiPacT A earth leakage current sensor
VigiPacT L earth leakage current sensor[Ithe] classically shielded thermal current 8A minimum load 10 mA at 12 V [Us] nominal supply voltage 220...240 V AC 50/60 Hz 55...110% power consumption 4VA Monitored distribution system 1000 V - AC at 50/60 Hz (maximum)
1000 V - AC at 400 Hz (maximum)grounding system IT
TN-S
TT[Uimp] nominal impulse withstand voltage 8kV reset Manual reset Complementary
test function Remote testing
Localtracing Electronics (continuous)
Power supply (continuous)
Relay/sensor connection (continuous)type of measurement Ground fault current internal measurement, range: 80...100% tamper resistance of settings Protected by a sealable cover wire stripping length Auxiliary power supply: 7 mm for upper connection
Error: 8 mm for lower connection
Relay test and error reset: 5 mm for lower connection
Sensor: 5 mm for upper connection
Voltage presence: 8 mm for lower connectiontightening torque Auxiliary power supply: 0.6 Nm upper
Error: 0.6 Nm lower
Relay test and error reset: 0.25 Nm lower
Sensor: 0.25 Nm upper
Voltage presence: 0.6 Nm lower9 mm screw pitch 6 standards EN/IEC 60947-2 Annex M
EN/IEC 60755
UL 1053
CAN/CSA C22.2 No. 144Width 54mm Height 81mm Depth 74mm Product weight 0.3kg IP protection degree IP40 on the front: conforming to EN/IEC 60529
IP30 on the side parts: conforming to EN/IEC 60529
IP20 on the connection terminals: conforming to EN/IEC 60529HR protection degree IK07 conforming to EN 50102 mechanical durability Fire resistance conforming to IEC 60695-2-1
IK protection 2 joules: IK07 conforming to EN 50102
Vibrations 13.2...100 Hz: 0.7 g
Vibrations 2...13.2 Hz: +/- 1 mmEnvironment
overvoltage category IV class of protection against electric shock Class II electromagnetic compatibility Conducted and radiated emissions: B CISPR 11
Conducted radio frequency immunity test: 3 conforming to IEC 61000-4-6
Electrostatic discharge immunity test: 4 conforming to IEC 61000-4-2
High energy conductive sensitivity: 4 conforming to IEC 61000- 4-5
Low energy conductive sensitivity: 4 conforming to IEC 61000-4-4
Radiation sensitivity: 3 conforming to IEC 61000-4-3relative humidity 95 % at 55 °C degree of pollution 3 conforming to IEC 60664-1 Nominal operating ambient temperature -35…70 °C Storage environmental conditions -55…85 °C Packaging units
Unit Type of Package 1 P.C.E. Number of Units in Package 1 One Package 1 Height 8.6cm Package 1 Width 9cm Package 1 Length 8cm Package 1 Weight 287g